GFP243-1200

Model GFP, Ground Fault Relay, Door Mount, 120VAC, without Interlock, with Form C Contacts, 100-1200 Amp Trip Current, Electromagnetic Industries

1,414.13 1414.13 USD 1,414.13

1,414.13

  • Brand
  • Model
  • Form Factor
  • Input Range
  • Input Frequency
  • Input Frequency
  • Tariff Code
  • ECCN

This combination does not exist.

GROUND FAULT CURRENT DETECTION

With Inverse Time Capability

Model GFP Relay

The GFP system is designed for electrical equipment protection, not for personnel protection

Application: 

These Class 1 (Model GFP) Ground Fault relays and sensors are used together to provide a system for detecting ground fault current in a grounded AC power system. When the system detects a ground fault that reaches a pre-selected current level and time delay, the relay initiates a trip signal for a shunt trip disconnect device to open and clear the fault.
The relays are also available with interlocks (for coordination of multiple devices in a system) and without interlocks (for single device systems).
The GFP non-interlock relays form/fit/function replacements for the BGFL Ground Fault relay without interlock.

  • Operating Range: Trip currents models are available for 5-60, 30-360, and 100-1200A. The time delay is adjustable from instantaneous to 1 second.
  • Input Power: 2VA plus shunt coil requirements. (Rated @ 120 VAC)
  • Input Withstand: 200,000 Amperes RMS for 3 cycles, 50/60 Hz.
  • Nominal Input Voltage: 120 Volts AC, 125 Volts DC, 48 Volts DC, 24 Volts DC
  • Frequency: 50/60 Hz
  • Ambient Temperature Range: -30 Deg C. to 60 Deg C.
  • Contact Ratings: 
    • Device Input Power: 120 VAC
    • Inrush: 10 A
    • Continuous: 3 A
  • Two (2) Styles “Standard” (without interlock) and “Zone Interlocking”
  • Integral test panel with “Push to Test” and “Shunt Trip Bypass” push-buttons for proper testing of device with the ability to trip or not to trip the protective device.
  • Power On Indication (LED)
  • Real time fault current level indicator(indicating actual value of trip set point)
  • Positive visual trip indicator.
  • Indication of fault current level at trip after unit has tripped.
  • Adjustable time delay with three time delay characteristics options
  • Discrete current threshold adjustment.
  • Panel or door mounted
  • Clear plastic cover
  • Electromechanical relay output positive “ON” and “OFF”
  • Operates with molded case power circuit breakers, bolted pressure switches, or fusible disconnect switches.
  • Optional “Form C” contacts
  • Meets NEC service entrance equipment standards.


Specifications

Brand Electromagnetic Industries
Model GFP
Form Factor Door Mount
Input Range 100-1200AAC
Input Frequency 50Hz, 60Hz
Tariff Code 8536.30.0000
ECCN EAR99