GFP241-60
Model GFP, Ground Fault Relay, Door Mount, 120VAC, with Interlock, 5-60Amp Trip Current, Electromagnetic Industries
GROUND FAULT CURRENT DETECTION
With Inverse Time Capability
Model GFP Relay
The GFP system is designed for electrical equipment protection, not for personnel protection
Application:
These Class 1 (Model GFP) Ground Fault relays and sensors are used together to provide a system for detecting ground fault current in a grounded AC power system. When the system detects a ground fault that reaches a pre-selected current level and time delay, the relay initiates a trip signal for a shunt trip disconnect device to open and clear the fault.
The relays are also available with interlocks (for coordination of multiple devices in a system) and without interlocks (for single device systems).
The GFP non-interlock relays form/fit/function replacements for the BGFL Ground Fault relay without interlock.
- Operating Range: Trip currents models are available for 5-60, 30-360, and 100-1200A. The time delay is adjustable from instantaneous to 1 second.
- Input Power: 2VA plus shunt coil requirements. (Rated @ 120 VAC)
- Input Withstand: 200,000 Amperes RMS for 3 cycles, 50/60 Hz.
- Nominal Input Voltage: 120 Volts AC, 125 Volts DC, 48 Volts DC, 24 Volts DC
- Frequency: 50/60 Hz
- Ambient Temperature Range: -30 Deg C. to 60 Deg C.
- Contact Ratings:
- Device Input Power: 120 VAC
- Inrush: 10 A
- Continuous: 3 A
- Two (2) Styles “Standard” (without interlock) and “Zone Interlocking”
- Integral test panel with “Push to Test” and “Shunt Trip Bypass” push-buttons for proper testing of device with the ability to trip or not to trip the protective device.
- Power On Indication (LED)
- Real time fault current level indicator(indicating actual value of trip set point)
- Positive visual trip indicator.
- Indication of fault current level at trip after unit has tripped.
- Adjustable time delay with three time delay characteristics options
- Discrete current threshold adjustment.
- Panel or door mounted
- Clear plastic cover
- Electromechanical relay output positive “ON” and “OFF”
- Operates with molded case power circuit breakers, bolted pressure switches, or fusible disconnect switches.
- Optional “Form C” contacts
- Meets NEC service entrance equipment standards.
Replaces
- BGFL259-60
Specifications
Brand | Electromagnetic Industries |
Model | GFP |
Form Factor | Door Mount |
Input Range | 5-60AAC |
Input Frequency | 50Hz, 60Hz |
Tariff Code | 8536.30.0000 |
ECCN | EAR99 |