BGFL159-1200 ITI

Model BGFL Ground Fault Relay, Panel Mount, 120VAC, Without Interlock, Trip Current 100-1200 Amp, ITI

2,028.75 2028.75 USD 2,028.75

2,028.75

  • Brand
  • Model
  • Input Range
  • Input Frequency
  • Input Frequency
  • Tariff Code
  • ECCN

This combination does not exist.

Model BGFL (Relay)

OPERATING RANGE:

  • Time delay from 0.10 to 1 second. (Adjustable)
  • Trip currents of 100-1200A. (-1200 Variants)

INPUT POWER:

  • 2 VA plus shunt coil requirements. Rated @ 120 Vac.

INPUT WITHSTAND:

  • 200,000 Amperes RMS for 3 cycles, 50/60 Hz.

NOMINAL INPUT VOLTAGE:

  • 120 Volts ac, 50/60Hz

FREQUENCY:

  • 50/60 Hz.

AMBIENT TEMPERATURE RANGE:

  • -30°C to +60°C

Only for use with GFL sensors.
Approximate weight 1.5 lbs.

These Class 1 Model BGFL Ground Fault Relays and Sensors are designed to form a system for detecting a ground fault current on a ground ac power system. When a ground fault exceeds a pre-selected Current level and Time Delay setting, the relay initiates a trip signal for a shunt trip disconnect device to open and clear the fault . This BGFL system is designed to provide protection for electrical equipment, not protection for personnel.

  • Meets NEC service entrance equipment standards.
  • Available in three basic styles, “Standard”, “Form C”, or “Zone Interlocking” for coordination of single or multiple ground fault devices in system.
  • Integral test panel with Push To Test and Shunt Trip Bypass pushing for ease in proper operational testing of the system, with or without tripping the protective device.
  • “Power On” LED indicator in cover.
  • Positive visual trip indicator, manual reset .
  • Infinitely adjustable Time Delay.
  • Discrete current threshold adjustment.
  • Panel or door mounting.
  • Rear terminal kit and clear plastic cover standard with door mounting.
  • Electromechanical relay output , positive “ON” and “OFF”.
  • Operates with molded case and power circuit breakers, bolted pressure switches, fusible disconnect switches.

CONTACT RATING: (120VAC Variants)

  • Inrush: 10A
  • Cont.: 3A

Specifications

Brand Instrument Transformers Inc
Model BGFL
Input Range 100-1200AAC
Input Frequency 50Hz, 60Hz
Tariff Code 8536.41.0050
ECCN EAR99