2VT469-120 EI

https://www.metersales.com/web/image/product.template/28632/image_1920?unique=8d174ad

Model 2VT469 120:120V Ratio PT/VT, 3Phase Open Delta, Electromagnetic Industries

413.00 413.0 USD 434.74

434.74

Not Available For Sale

  • Brand
  • Model
  • Input Range
  • Input Frequency
  • Accuracy
  • Output
  • Tariff Code
  • ECCN
  • Insulation Level
  • PT/VT Group
  • PT/VT Turns Ratio
  • PT/VT Thermal Rating
  • PT/VT Thermal Rating
  • PT/VT Rec. Primary Fuse Rating

This combination does not exist.

The Model 2VT469 is a two transformer assembly in one case with all terminals accessible for an Open Delta connection. 

These transformers are encased in a thermoplastic case with the core and windings encapsulated in resin. They are designed for line to line operation but may also be used in line to neutral or line to ground configuration at 58% of rated voltage. 

It is recommended that a 0.4 Amp fuse be used in the secondary to protect the transformer. 

FREQUENCY: 60 Hz 

STANDARD SECONDARY VOLTAGE: 120 VAC 

INSULATION LEVEL: 600 Volts, 10Kv BIL Full Wave 

ACCURACY CLASS: +/- 1% at all burdens up to 5VA at 1.0 and 0.95 P.F. 

THERMAL RATING: 40 VA @ 30 C. amb 27 VA @ 55 C. amb 

  • Terminals are No. 6-32 screws with cup washers. 
  • Approximate weight: 1.5 lbs.

Specifications

Product
Brand Electromagnetic Industries
Model 2VT469
Input Range 120VAC
Input Frequency 60Hz
Accuracy 1% Class up to 5VA from 0.95 to 1.0 PF
Output 120VAC
Tariff Code 8504.31.0000
ECCN EAR99
Insulation Level 600V, 10kV BIL full wave
Potential Transformers
PT/VT Group Group 1. Rated Voltage: 100% L-L or L-G
PT/VT Turns Ratio 1/1
PT/VT Thermal Rating 40VA at 30°C amb., 27VA at 55°C amb.
PT/VT Rec. Primary Fuse Rating 1.0 A