Distributed By:
Instrument Meter Specialties, Inc
Phones: 800-926-3837....818-841-2417... FAX 818-841-2379
  We accept:
 Visa - Mastercard - American Express-Discover

IMSLogo.gif (3426 bytes)

Prova 2009 AC/DC True RMS Watt Clamp

AC+DC 1200KW
• DC/AC 2000A & ANALOG OUTPUT
• Cable Ø 55mm
• True RMS


Features
• Bus Bar 64mm(D) x 25mm(W)
• kW, DCA One Touch Zero
• Continuity
• 4000 COUNTS
• Fast Bar-Graph
• Max/Min/Hold
• Relative Measurement
• Autorange A, V, °C, kW

Specifications for Prova 2009 (IEC CAT. III 600V)

Jaw Opening: Cable Ø55mm
Bus Bar 65mm (D) x 24mm (W)
Power Source: One 006p 9V or IEC 6F22 
or NEDA 1604 Battery
Operating Temperature: 0°C to 40°C (32°F to 104°F)
Operating Humidity: Less than 80% RH
Dimensions: 271mm(L) x 112mm(W) x 46mm(H)
10.7”(L) x 4.4”(W) x 1.8”(H) 
Weight: 647g/22.8 oz (Battery included)

Electrical Specification (23°C ± 5°C)
DC Current (Autorange & Manual)
Range: 400A/2500A
Resolution: 0.1A/1A
Accuracy: ± 1.5% rdg ± 3 dgts
Overload Protection: 3000A
AC + DC 250V POWER 
(Autorange & Manual)
Range: 40KW/400KW
Resolution: 0.01KW/0.1KW
Accuracy: ± 2.5% rdg ± 5 dgts
Overload Protection: 800VAC 3000A
AC + DC 600V POWER 
(Autorange & Manual)
Range: 400KW/1200KW
Resolution: 0.1KW/1KW
Accuracy: ± 2.5% rdg ± 5 dgts
Overload Protection: 800VAC 3000A
Accessories included: Carrying Case, 
Instruction Manual, Safety Test Lead, 
Battery, TPK 
01 Thermocouple
ANALOG OUTPUT (Autorange & Manual)
Range: 400A/2500A
Resolution: 1mV/A
Accuracy: ± 2.5% rdg ± 0.5A/± 2.5% rdg ± 5A
Overload Protection: 600VAC

AC Current (Autorange & Manual, True RMS)
Range: 400A/2100A(0~1000)/2100A(1000~2100)
Resolution: 0.1A/1A
Accuracy: ± 1.5% rdg ± 5 dgts/± 2.0% rdg ± 5 dgts/
± 2.5% rdg ± 5 dgts (50/60Hz)
± 2.0% rdg ± 5 dgts/± 2.5% rdg ± 5 dgts/
± 3% rdg ± 5 dgts (40-400Hz)
Overload Protection: 3000A
ANALOG OUTPUT (Autorange & Manual)
Range: 400A/2100A
Resolution: 1mV/A
Accuracy: ± 2.5% rdg ± 0.5A/± 2.5% rdg ± 5A
Overload Protection: 600VAC
DC Voltage (Autorange & Manual, Overload Protection 800VAC for all Range)
Range: 400mV/4V/40V/400V/600V
Resolution: 0.1mV/0.001V/0.01V/0.1V/1V
Accuracy: ± 1.5% rdg ± 3 dgts
Input Impedance: 10M?/5M?
AC Voltage (Autorange & Manual, True RMS, 
Input Impedance 5M? for all Range)
Range: 4V/40V/400V/600V
Resolution: 0.001V/0.01V/0.1V/1V
Accuracy: ± 1.5% rdg ± 5 dgts
Overload Protection: 800VAC
Audible Continuity
Range: 400?
Continuity Beeper: =40? (approx.)
Open Circuit Voltage: =0.5V
Overload Protection: 600VAC
TEMP K TYPE °C
(Autorange & Manual, °F Optional)
Range: -50~400°C/ 400~1000°C
Resolution: 0.1°C/1°C
Accuracy: ± 1% rdg ± 1°C
Overload Protection: 600VAC

Back to MTP  Price List