Distributed By: Instrument Meter Specialties, Inc Phones: 800-926-3837....818-841-2417... FAX 818-841-2379 Visa - MasterCard - American Express |
|
ITI Current Transformers Model 2 - Window Diameter 1.13" |
||
| APPLICATION: Generally for Ammeter use only |
FREQUENCY: 50-400 Hz |
INSULATION
CLASS: 0.5 kv B I L 10 kv full wave |
|
|||||
Specifications: *Flexible
Leads are UL 1015 105°C, CSA Approved, #16, 24" long *Specify |
|||||
|
Catalog |
Current |
Model 2 |
Model 2 DRL |
||
|
Accuracy |
Burden VA |
Accuracy |
Burden VA |
||
| 2 RL-500 & 2SFT-500 |
50.5 |
± 3% | 2.0 | ± 2% |
1.5 |
| 2 RL-600 & 2SFT-600 | 60:5 | ± 2% | 2.0 | ± 1% | 2.5 |
| 2 SFT-750 | 78:5 | ± 2% | 2.0 | ± 1% | 3.5 |
| 2 **-800 | 80:5 | ± 2% | 2.0 | ± 1% | 4.0 |
| 2 RL-101 & 2SFT-101 | 100:5 | ± 1% | 2.0 | ± 1% | 5.0 |
| 2 **-121 | 120:5 | ± 1% | 2.5 | ± 1% | 5.0 |
| 2 **-1250 | 125:5 | ± 1% | 2.5 | ± 1% | 5.0 |
| 2 RL-151 & 2SFT-151 | 150:5 | ± 1% | 4.0 | ± 1% | 8.0 |
| 2 RL-201 & 2SFT-201 | 200:5 | ± 1% | 4.0 | ± 1% | 10.0 |
| 2 RL-251 & 2SFT-251 | 250:5 | ± 1% | 6.0 | ± 1% | 12.5 |
| 2 RL-301 & 2SFT-301 | 300:5 | ± 1% | 8.0 | ± 1% | 15.0 |
Return to
ITI Contents
Copyright ©20001 Instrument
Meter Specialties, Inc.
Burbank, CA 91506 USA