Applications

Personnel Protection (typically 5mA) Senses low fault currents and alarms to shut power before injury occurs.

Equipment Protection (typically 30mA) When personal protection is not an issue, select a higher setpoint to protect equipment or product.

Regulatory Approval

Meet requirements by industry groups and governments for Ground Fault Protection.

Features

Broad Range of Options to Match Application Needs:

— Choice of NO/NC solid-state switch and mechanical relay outputs.

— Normally energized or normally de-energized contacts.

— Latching outputs for controlling contactors; auto-reset option for control of shunt trip breakers.

— Noise-immune option for use in EMI/RFI sensitive environments.

Setpoint Options Maximize Ease-of-Use:

— Field-selectable 5mA, 10mA or 30mA setpoints (AG3 “Tri-set” model only) makes user-adjustable setpoint fast and convenient.

— Single, factory-adjusted setpoint can be fixed from 5mA to 950mA when ordering.

Compatible with Standard Equipment

— Applicable on most 1Φ and 3Φ systems.

— Ideal for use with shunt trip breakers or contactors.

— Magnetically isolated from monitored circuit and control power.

Agency Approved

UL, CUL and CE acceptance worldwide.

Output Table

Normally Energized Models (–FS Option)

Protection from faults and loss of control power.

 

                                            Control Power Applied

                                        No Power   No Fault     Fault

N.C. Normally Closed        Closed        OPEN      Closed

N.O. Normally Open          Open       CLOSED      Open

 

Normally De-energized Models (–NF Option)

Protection from faults only when control power is applied.

 

                                             Control Power Applied

                                        No Power   No Fault     Fault

N.C. Normally Closed        Closed     CLOSED      Open

N.O. Normally Open           Open        OPEN        Closed

Specifications

Dimensions

Setpoint Range

“Single-Set” Models Factory adjusted and sealed

                  AG1: 5–100mA, specify when ordering

                  AG2: 80–950mA, specify when ordering

“Tri-Set” Models

                   5, 10 & 30mA jumper select

Output Isolated Dry Contact

Output Rating

 Solid State AC Switch: 1A @ 240VAC

Solid State DC Switch: 0.15A @ 30VDC

Off State Leakage < 10μA

Response Time

200 ms @ 5% above setpoint

60 ms @ 50% above setpoint

15 ms @ 500% above setpoint

Isolation Voltage Up to 1,250VAC (monitored circuit)

Frequency Range 50–400Hz (monitored circuit)

Sensing Aperture 0.75" (19.1mm) dia., up to 4" (100mm)

dia. available, consult factory.

Power Supply

120VAC (55-110% of nominal voltage)

24VAC/DC (+/–10% of nominal voltage)

Green LED = power (all models)

Case UL 94V-O Flammability Rated

Environmental 5 to 158°F (–15 to 70°C), 0-95% RH, non-condensing

Safety UL 1053, Class 1 Recognized, CE*

*Most option combinations are UL recognized.

Ordering Information

Example: AG1-NOAC-120-005-FS

Ground fault sensor with normally open solid state output, 120VAC power supply, 5mA setpoint, fail safe version.

Dimensions