Instrument Meter Specialties

2108 B West Magnolia Blvd
Burbank, CA 91506
Phone: 800-926-3837 FAX: 818-841-2379

Applications

Motor Protection

– Serves as an electronic proof-of-operation; detects current draw changes in motors when they encounter problems such as pumps running dry or pending bearing failure.

– Non-intrusive, less expensive to install than differential pressure flow sensors or thermal switches. Much quicker response time than Class 10 overload relays.

High Inrush or Temporary Overload Current

– Start-up/delay timer provides 2 second delay to avoid nuisance tripping from high inrush or short

overload conditions.

Features

Fixed Start-up/Delay Timer

– Factory calibrated trip timer set to 2 seconds to eliminate nuisance alarms due to start-up inrush or temporary overcurrent conditions.

Choice of N.O./N.C. Electro-mechanical Relay Output

– Contact rating of 10A@240VAC provides adequate switching capacity for use in most motor control systems.

Improved Ease of Installation and Use

– Eliminates need for separate time delay relay Choice of 24VAC/DC or 120VAC supply models

LED provides indication of trip point contact status Setpoint adjustable from 1-50A

Industrial Grade Performance

– 0.5% accuracy, precise time delay setpoint, constant hysteresis, linear response and low frequency capability

Agency Approved

– UL, CE approvals pending

Specifications

Dimensions

Power Supply 24VAC/VDC (+/- 10%), 2VA max

Output Electro-Mechanical SPDT Relay, Auto-Reset

Output Rating Normally Open 10A@240VAC

Trip Point Range Adjustable 1-50A

Time Delay 2.0 seconds (fixed)

Tolerance +/- 1%

Input Range 0-50A

Max Inrush Current 500A (5 sec. duration)

Accuracy 0.5%

Hysteresis 5% (Constant)

Isolation Voltage 1,250 VAC (monitored)

Frequency Range 6-100 Hz

Case UL 94V-O Flammability Rated

Environmental -4 to 122°F (–20 to 50°C), 0-95% RH, non-condensing

Sensing Aperture 0.75" (19.1mm) diameter

Listings UL Listed 508, CE (pending)

Ordering Information

Example: ASXP1-NOAC-24U-FL

AC Current switch, fixed 2 sec. delay, N.O. 10A@240VAC output,

24VAC/VDC supply, solid-core enclosure.

Dimensions