A pplications■ Motor Protection – Serves as an electronic proof-of-operation; detects current draw changes in motors when they encounter problems such as pumps running dry or pending bearing failure. – Non-intrusive, less expensive to install than differential pressure flow sensors or thermal switches. Much quicker response time than Class 10 overload relays. ■ High Inrush or Temporary Overload Current – Adjustable start-up/delay timer allows 0-15 second delay to eliminate nuisance trips from high inrush or short overload conditions.
F eatures■ Adjustable Start-up/Delay Timer– Field-adjustable from 0-15 seconds to eliminate nuisance alarms due to start-up inrush or temporary overcurrent conditions. ■ Choice of N.O./N.C. AC or Universal Outputs– Contact ratings of 1.0A@240VAC or universal outputs of 0.15A@240VAC/VDC (N.O. models) and 0.2A@135VAC/VDC (N.C. models) for use with most standard motor control systems. ■ Improved Ease of Installation and Use– 1.0A rating eliminates need for time delay relay – Self-powered, split-core models simplify installation – Status LED provides visual indication of setpoint trip and contact action. ■ Industrial Grade Performance– Constant hysteresis and linear response characteristic enhance accuracy to setpoint ■ Agency Approved– UL, CE approvals pending
S pecificationsPower Supply None -- Self-poweredOutput Isolated Solid-State SwitchOutput Rating ■ NOAC/NCAC: 1A @ 240VAC■ NOU: N.O. 0.15A @ 240VAC or VDC■ NCU: N.C. 0.20A @ 135VAC or VDCResponse Time Adjustable 0.2 to 15 seconds Off State Leakage < 10 micro Amps Setpoint Ranges Jumper Selectable: 1.5-12A, 12-55A, 50-200A Hysteresis 5% (Constant) Overload (1 sec. duration) ■ 1.5-12A Range: 600A■ 12-55A Range: 800A■ 50-200A Range: 1,200AIsolation Voltage 5,000 VAC (tested) Frequency Range 50-100 Hz Case UL 94V-O Flammability Rated Environmental 5 to 158°F (–15 to 70°C), 0-95% RH, non-condensing Listings UL Listed 508, CE (pending) O rdering InformationExample: ASX-NOAC-SP Current Switch w/Adjustable Time Delay, N.O. 1.0A@240VAC output, Jumper Selectable Input Ranges, Split-core Enclosure.
|
||