Instrument Meter Specialties

2108 B West Magnolia Blvd
Burbank, CA 91506
Phone: 800-926-3837 FAX: 818-841-2379

Applications

Motor Protection

– Serves as an electronic proof-of-operation; detects current draw changes in motors when they encounter problems such as pumps running dry or pending

bearing failure.

– Non-intrusive, less expensive to install than differential pressure flow sensors or thermal switches. Much quicker response time than Class 10 overload relays.

High Inrush or Temporary Overload Current

– Adjustable start-up/delay timer allows 0-15 second delay to eliminate nuisance trips from high inrush or short overload conditions.

Features

Adjustable Start-up/Delay Timer

– Field-adjustable from 0-15 seconds to eliminate nuisance alarms due to start-up inrush or temporary overcurrent conditions.

Choice of N.O./N.C. AC or Universal Outputs

– Contact ratings of 1.0A@240VAC or universal outputs of 0.15A@240VAC/VDC (N.O. models) and 0.2A@135VAC/VDC (N.C. models) for use with most standard motor control systems.

Improved Ease of Installation and Use

– 1.0A rating eliminates need for time delay relay

– Self-powered, split-core models simplify installation

– Status LED provides visual indication of setpoint trip and contact action.

Industrial Grade Performance

– Constant hysteresis and linear response characteristic enhance accuracy to setpoint

Agency Approved

– UL, CE approvals pending

Specifications

Dimensions

Power Supply None -- Self-powered

Output Isolated Solid-State Switch

Output Rating

NOAC/NCAC: 1A @ 240VAC

NOU: N.O. 0.15A @ 240VAC or VDC

NCU: N.C. 0.20A @ 135VAC or VDC

Response Time Adjustable 0.2 to 15 seconds

Off State Leakage < 10 micro Amps

Setpoint Ranges Jumper Selectable: 1.5-12A, 12-55A, 50-200A

Hysteresis 5% (Constant)

Overload (1 sec. duration)

1.5-12A Range: 600A

12-55A Range: 800A

50-200A Range: 1,200A

Isolation Voltage 5,000 VAC (tested)

Frequency Range 50-100 Hz

Case UL 94V-O Flammability Rated

Environmental 5 to 158°F (–15 to 70°C), 0-95% RH, non-condensing

Listings UL Listed 508, CE (pending)

Ordering Information

Example: ASX-NOAC-SP

Current Switch w/Adjustable Time Delay, N.O. 1.0A@240VAC output, Jumper Selectable Input Ranges, Split-core Enclosure.

 

Dimensions